Honeywell Kromschroder BCU 370 Burner Control Unit

  • Monitors: low gas, high gas, and low air pressure switches
  • Pre-purge/post-purge fan and air valve control
  • Optional integrated ignition transformer
  • Optional PROFIBUS communications
  • Integrated front panel display indicates fault and operating status
  • Manual-mode operation for initial burner set-up
  • Front Panel PC interface for programming diagnostics, and data logging
  • Approvals: CE, CSA, FM and UL

Description

The BCU 370 burner control unit controls, ignites and monitors industrial forced draught burners of unlimited capacity in intermittent or continuous operation.

It can be used for directly ignited forced draught burners or forced draught burners ignited with pilot burner. The BCU 370 activates the blower and sets the connected butterfly valve to pre-purging and ignition position. After pre-purge and burner start, the Enable signal is issued to an external controller which positions the butterfly valve in accordance with the output demand. Post-purge occurs after the end of burner operation. The burner control unit BCU 370 monitors the gas and air pressure. An optionally integrated tightness control function checks the valves with an external gas pressure switch.

Application: Single packaged burner applications where the burner control is located locally to the burner.

Technical Documentation

BCU 370 Burner Control Unit Technical Documentation